CPSC official recall · 01503
CPSC, Liebert Corp. Announce Recall of Cooling System
重要:以下安全事实保留 CPSC 官方英文原文,避免翻译改变含义。请通过右侧官方公告确认行动要求。
危险说明 Hazard
- An electric heating element inside the system, that is used primarily in the dehumidification process, can short circuit and produce sparks, posing a smoke and fire risk.
受影响产品
Mini-Mate2 Environmental Control Units
Units:About 1,500
官方描述 Description
The environmental control units are used as a cooling system in computer rooms. The recalled units are 277 volts and 1.5, 2 and 3 tons with electric reheat. The units are mounted in the ceiling and use ducts or special distribution grills to distribute the air.
事故与伤害 Incidents / Injuries
- No injuries have been reported.
官方补救措施 Remedy
- For more information about the recall, contact Liebert Corp. for instructions on disconnecting the reheat assembly. Liebert Corp. will install and replace the heating element. Liebert Corp. sent recall notices to known purchasers.
消费者联系信息
For more information about the recall, contact Liebert Corp. at (800) 543-2778 between 8 a.m. and 5 p.m. ET Monday through Friday.
相关企业
制造商:Liebert Corp., of Columbus, Ohio
零售商:Liebert Corp. sold these units nationwide, from January 1998 through August 2000, for between $3,000 and $8,000.