CPSC, Fire Control Instruments Announce Recall for Audio Evacuation Units

召回日期:2003-10-30官方最后发布:2025-03-24适用地区:美国
重要:以下安全事实保留 CPSC 官方英文原文,避免翻译改变含义。请通过右侧官方公告确认行动要求。

危险说明 Hazard

  • The AEU can enter a "sleep" mode, where it does not communicate with the system. When this occurs, audible evacuation signals associated with the failed AEU will not operate and building occupants may not be warned of an emergency.

受影响产品

Audio Evacuation Unit
Units:276

官方描述 Description

All FCI AEUs (part number 1100-1171) manufactured prior to April 12, 2003. These AEUs are used in FireVac 7200 System Control Units. A label in the left center of the circuit board reads "FCI 7200" and "AEU." All V5 versions below V5.2-008 and V6 versions below V6.0.14 are included in the recall.

事故与伤害 Incidents / Injuries

  • FCI has received seven reports of AEUs unexpectedly entering a "sleep" mode. No injuries have been reported.

官方补救措施 Remedy

  • FCI will provide a new software chip set for each FireVac System, at no charge.

消费者联系信息

Distributors who do not receive the new software chip set or who have additional questions should contact their customer service representative at (800) 633-1311 between 8 a.m. and 5 p.m. ET, Monday through Friday.

相关企业

制造商:Fire Control Instruments, of Westwood, Mass.

制造国家/地区:United States

零售商:To FCI distributors nationwide, from January 1998 through April 11, 2003, for a list price of $825.