CPSC official recall · 04508

CPSC, Notifier Announce Recall for Fire Alarm Panels

召回日期:2003-10-30官方最后发布:2025-03-24适用地区:美国
重要:以下安全事实保留 CPSC 官方英文原文,避免翻译改变含义。请通过右侧官方公告确认行动要求。

危险说明 Hazard

  • The AEU can enter a "sleep" mode, where it does not communicate with the system. When this occurs, audible evacuation signals associated with the failed AEU will not operate and building occupants may not be warned of an emergency.

受影响产品

Fire Alarm Control Panel
Units:6,000

官方描述 Description

The fire alarm control panel includes the central processing unit (CPU-2020 and CPU-2) and Display Interface Assembly (DIA-2020 and DIA-2) components of Notifier model AM2020 and AFP1010 fire alarm control panels with date codes from 0100 to 2003 and firmware version 3.0 and 3.01. The date codes appear on the back outer edge of the PC boards.

事故与伤害 Incidents / Injuries

  • Notifier has received eight reports of trouble signals alarming. In each case the problem was identified and corrected. No injuries have been reported.

官方补救措施 Remedy

  • Notifier will provide an upgraded CPU firmware set for each AM2020 and AFP1010 panel, at no charge.

消费者联系信息

Distributors should contact their Notifier customer service representative at (800) 289-3473 between 8 a.m. and 5 p.m. ET, Monday through Friday to receive the firmware upgrade.

相关企业

制造商:Notifier, of Northford, Conn.

制造国家/地区:United States

零售商:Notifier distributors nationwide, from January 2000 through May 2002. The list price for the CPU and DIA combination for the model AM2020 is about $6,400, and the list price for the CPU and DIA combination for the model AFP1010 is about $3,370.