CPSC official recall · 07565

Gamewell-FCI Recalls to Upgrade Software Used with Fire Alarm System Control Panels

召回日期:2007-07-27官方最后发布:2014-05-23适用地区:美国
重要:以下安全事实保留 CPSC 官方英文原文,避免翻译改变含义。请通过右侧官方公告确认行动要求。

危险说明 Hazard

  • The software in the fire alarm system could fail to recognize when a detector needs servicing as a result of the buildup of dust, dirt, or other environmental pollutants, which could result in the system failing to respond in the event of a fire.

受影响产品

Gamewell-FCI 600 Series SmartScan Fire Alarm Control Panels
Units:About 1,100

官方描述 Description

The software upgrade involves the Gamewell-FCI model 600 Series control panel using System Sensor compatible line cards, SmartScan. These panels are components of the Gamewell-FCI 600 Series fire alarm system. They provide the signaling line circuits and display information for the system.

事故与伤害 Incidents / Injuries

  • Gamewell-FCI has received no reports of the firmware failing to operate in the event of a fire.

官方补救措施 Remedy

  • Gamewell-FCI is contacting customers directly and providing a free firmware software upgrade.

消费者联系信息

For additional information, contact Gamewell-FCI at (800) 633-1311 between 8 a.m. and 5 p.m. ET Monday through Friday, or go to the firm's Web site at www.gamewell-fci.com

相关企业

制造商:Gamewell-FCI, of Northford, Conn.

制造国家/地区:United States

零售商:Authorized distributors nationwide from October 2004 through May 2007 for between about $400 and $3,500. Authorized distributors resold and installed the control panels for commercial end users in facilities such as hotels and office buildings.