Gamewell-FCI Recalls to Upgrade Software Used with Fire Alarm System Control Panels
危险说明 Hazard
- The software in the fire alarm system could fail to recognize when a detector needs servicing as a result of the buildup of dust, dirt, or other environmental pollutants, which could result in the system failing to respond in the event of a fire.
受影响产品
官方描述 Description
The software upgrade involves the Gamewell-FCI model 600 Series control panel using System Sensor compatible line cards, SmartScan. These panels are components of the Gamewell-FCI 600 Series fire alarm system. They provide the signaling line circuits and display information for the system.
事故与伤害 Incidents / Injuries
- Gamewell-FCI has received no reports of the firmware failing to operate in the event of a fire.
官方补救措施 Remedy
- Gamewell-FCI is contacting customers directly and providing a free firmware software upgrade.
消费者联系信息
For additional information, contact Gamewell-FCI at (800) 633-1311 between 8 a.m. and 5 p.m. ET Monday through Friday, or go to the firm's Web site at www.gamewell-fci.com
相关企业
制造商:Gamewell-FCI, of Northford, Conn.
制造国家/地区:United States
零售商:Authorized distributors nationwide from October 2004 through May 2007 for between about $400 and $3,500. Authorized distributors resold and installed the control panels for commercial end users in facilities such as hotels and office buildings.