Fire Alarm Control Panels Recalled by Notifier Due to Alert Failure
危险说明 Hazard
- The software in the fire alarm system could fail to process an alarm condition which could result in the system failing to respond in the event of a fire.
受影响产品
官方描述 Description
This recall involves the Notifier brand operating system firmware control panels in fire alarms. The control panel is black or red with a silver screen. The panels control display and emergency communications. "NOTIFIER" or "NOTIFIER by Honeywell" is printed on the front of the fire alarm unit. This recall includes the following model numbers: Firmware version 11.2.2 for NFS2-640 and NFS-320 control panels and firmware version 3.14.1 for and NFS-640 control panels.
事故与伤害 Incidents / Injuries
- None reported.
官方补救措施 Remedy
- Distributors should immediately contact the company for replacement software. All known users of have been contacted.
消费者联系信息
For additional information, contact Notifier at (800) 289-3473 between 8 a.m. and 5 p.m. ET Monday through Friday or visit the company's Web site at www.notifier.com
相关企业
制造商:Notifier, of Northford, Conn.
制造国家/地区:United States
零售商:Authorized distributors to commercial end-users. The products were not sold at retail, but version 11.2.2 was available for download on www.magni-fire.com, a secure Web site accessible only to Notifier customers from May 2008 through July 2008 at no charge.