CPSC official recall · 12156

Gems Sensors Recalls Pressure Transducers Used in Fire Pump Controllers Due to Risk of Failure in a Fire

召回日期:2012-04-24官方最后发布:2016-04-18适用地区:美国
重要:以下安全事实保留 CPSC 官方英文原文,避免翻译改变含义。请通过右侧官方公告确认行动要求。

危险说明 Hazard

  • The transducer can fail to accurately detect water pressure in a fire suppression sprinkler system. This could cause the sprinkler system to fail to activate and pump water to the sprinklers in the event of a fire.

受影响产品

Gems 3100 Pressure Detectors/Transducers
Units:About 25,000

官方描述 Description

The Gems 3100 Pressure Transducer is used to detect pressure in a range of applications, including the detection of water pressure as part of a fire pump controller in a fire suppression sprinkler system. The transducer has "Gems Sensors & Controls," as well as the 18-digit part number, printed on a label affixed to the center of the transducer. Part numbers beginning with "3100" are included in this recall.

事故与伤害 Incidents / Injuries

  • None.

官方补救措施 Remedy

  • Contact Gems to receive enhanced twice monthly inspection instructions and information about a free replacement transducer, when warranted. End-users who use the 3100 Pressure Transducer in other applications in which water pressure is measured should contact Gems to determine if their units are affected.

Options:New Instructions · Replace

消费者联系信息

For additional information, call the company toll-free at (855) 877-9666, between 8 a.m. and 4:30 p.m. ET, Monday through Friday, or visit the firm's website at http://www.gemssensors.com