CPSC official recall · 15050

Schneider Electric Recalls PowerPact J-Frame Circuit Breakers Due to Fire, Burn, Electrical Shock Hazards

召回日期:2014-12-18官方最后发布:2015-05-11适用地区:美国
重要:以下安全事实保留 CPSC 官方英文原文,避免翻译改变含义。请通过右侧官方公告确认行动要求。

危险说明 Hazard

  • The circuit breaker will not trip during an overload condition, posing a risk of fire, burns and electrical shock.

受影响产品

Circuit breakers
Units:About 62,500

官方描述 Description

The recall involves PowerPact J-frame molded case circuit breakers with thermal-magnetic trip units. The circuit breakers are made of black plastic and have a three-position breaker handle that indicates whether the breaker is off, on or tripped. The recalled circuit breakers are rated for 150 to 250 amps, have interruption ratings of D, G, J, L and R. They were manufactured in two pole and three pole configurations with either lug-in/lug-out or plug-in (I-Line) style connectors. Brand name "Schneider Electric" or "Square D" is on a yellow sticker above the breaker handle and on the top of a label on the side of the circuit breaker. A label on the front of the circuit breaker to the left of the breaker handle has the catalog number at the top. The number also appears on a label on the side of the breaker. Schneider Electric catalog numbers begin with "NJ" and Square D catalog numbers begin with "J." A label on the front of the circuit breaker to the right of the breaker handle has the date code in the lower right corner. Recalled circuit breakers were manufactured from March 26, 2014 through September 26, 2014 and have date codes 14131 through 14395. The date codes are in the YYWWD format (example: 14131 = year 2014, week 13, day of the work week 1/ Monday). Breakers with following catalog numbers are being recalled: Catalog Number Breaker Type (N)JDX26XXX 2 Pole (N)JGX26XXX 2 Pole (N)JJX26XXX 2 Pole (N)JLX26XXX 2 Pole (N)JDX36XXX 3 Pole (N)JGX36XXX 3 Pole (N)JJX36XXX 3 Pole (N)JLX36XXX 3 Pole (N)JRX36XXX 3 Pole

事故与伤害 Incidents / Injuries

  • None reported

官方补救措施 Remedy

  • Consumers should immediately stop using the recalled circuit breakers and contact Schneider Electric for either a free replacement circuit breaker and a credit of up to $300 per address to cover labor costs for installation by a certified electrician or a handle update kit and a credit of up to $150 per address to cover labor costs for installation by a certified electrician.

Options:Replace · Repair

消费者联系信息

Schneider Electric USA at (800) 634-8730 any time or online at www.schneider-electric.com and click on Customer Notifications for more information.

相关企业

制造商:Schneider Electric USA Inc., of Columbia, Mo., and Tlaxcala, Mexico

制造国家/地区:United States;Mexico

零售商:Authorized Schneider Electric distributors, original equipment manufacturers and in factory assembled panel boards from March 2014 through September 2014 for between $2,900 and $11,200.