Gamewell-FCI Recalls Fire Alarm Panels Due to Failure to Alert of a Fire, Smoke or CO
重要:以下安全事实保留 CPSC 官方英文原文,避免翻译改变含义。请通过右侧官方公告确认行动要求。
危险说明 Hazard
- When configured in a certain way, the panels can become non-responsive and connected detectors in the area can fail to detect and respond to an alarm.
受影响产品
Gamewell-FCI fire alarm panels (ILI-MB-E3 and ILI-S-E3)
Units:About 1,000
官方描述 Description
This recall is for the ILI-MB-E3 and ILI-S-E3 Gamewell-FCI fire alarm panels in commercial buildings. This issue is limited to a specific configuration of Signaling Line Circuit (SLC) devices. To occur, the SLC must include at least two of the following detectors in any combination: Acclimate, 4-Warn, Photo/CO and iFAAST. The issue would occur only if the detectors are addressed within the same FlashScan polling group. Detectors installed in a different combination are not affected.
事故与伤害 Incidents / Injuries
- No incidents or injuries have been reported.
官方补救措施 Remedy
- Consumers should immediately contact the distributor to obtain the free repair, a firmware upgrade.
Options:Repair
消费者联系信息
Gamewell-FCI at 800-274-4324 from 7 a.m. to 7 p.m. ET Monday through Friday or online at www.gamewell-fci.com and click on "Safety Recall" for more information.