CPSC official recall · 21177

dormakaba Recalls Delayed Egress Locks Due to Risk of Entrapment in an Emergency

召回日期:2021-08-11官方最后发布:2021-08-11适用地区:美国
重要:以下安全事实保留 CPSC 官方英文原文,避免翻译改变含义。请通过右侧官方公告确认行动要求。

危险说明 Hazard

  • The lockset can fail to open, posing an entrapment hazard and inability to vacate a location in an emergency.

受影响产品

Delayed Egress Locks
Units:About 2,400

官方描述 Description

This recall involves dormakaba Delayed Egress Locks with model number DE8310 found on the inside of the wiring cavity cover plate. These locks detect when pressure is applied to a door and are set with a release delay of 15 or 30 seconds. The recalled locks include an internal or external alarm sounder, key switch for reset and override, and a building code sign for single out swinging doors. Delayed egress locks are typically used on perimeter exit doors and internal fire doors to discourage or delay unauthorized exit while providing a safe means of escape during a fire or other catastrophic emergency.

事故与伤害 Incidents / Injuries

  • The firm has received reports of 56 incidents with the recalled locks. No injuries have been reported.

官方补救措施 Remedy

  • Facilities using the recalled locks should contact the firm for instructions on receiving a free repair of the firmware by a technician.

Options:Repair

消费者联系信息

dormakaba at 800-265-6630 from 8 a.m. to 5 p.m. ET Monday through Friday, email at DE8310.Recall@dormakaba.com or online at dormakaba.us and search for "recall" or "DE8310" for more information or here.

相关企业

制造商:Shanghai One Top Corporation, of Shanghai, China

制造国家/地区:China

进口商:dormakaba USA Inc., of Indianapolis, Ind.

零售商:Installed by contractors nationwide from October 2019 through March 2021 for between $1,200 and $1,400.